Apartments over a storefront in Maryland: when the upstairs conversion needs fire sprinklers and which standard the building gets.

Putting apartments over a shop in Maryland adds a residential use to the building, and the building code the state adopts calls for sprinklers throughout any building that has one. With the shop still open downstairs the building is mixed use and is designed to NFPA 13. A building that is all apartments, four stories or fewer, can use NFPA 13R.

That is the short version. The rest of this page is for the investor or the general contractor who just bought three floors on a Baltimore City main street, in downtown Frederick, on Main Street in Annapolis or Ellicott City, or along the avenue in Hyattsville or Silver Spring, and needs to know what the upstairs does to the whole building.

What makes the building mixed use

The building code sorts every space into a group by what goes on in it. A store is Group M. An office is Group B. A restaurant is Group A-2. Apartments are Group R, and a building with more than two dwelling units where people live full time is Group R-2. Keep the shop on the street floor and build apartments above it, and the building holds two groups under one roof. That is all mixed use means here. Nobody has to call it that on the listing for the plan reviewer to treat it that way.

The upstairs is usually the part that changes. Old main street buildings carried storage, an office or an empty floor over the shop for decades. Turning those floors into apartments is a change of occupancy, the same kind of event as a store turning into a restaurant, and it puts the building in front of the county for a fresh look.

When the conversion needs sprinklers

Maryland’s building standards adopt the 2021 International Building Code, and each county enforces it with its own amendments. The residential rule in that code is one of the shortest in the sprinkler chapter. An automatic sprinkler system goes throughout every building with a Group R fire area. There is no square footage to stay under and no unit count to stay under. Compare that with the shop downstairs, which on its own could run to 12,000 square feet before the same chapter asked for sprinklers.

Read the word throughout twice. The rule covers the building, so the storefront that never had a head in its ceiling gets them along with the apartments. The tenant downstairs needs to hear that before the lease renewal, because pipe is going through the shop.

An old building is still an old building, and the county reviewer decides how the rule lands on a change of occupancy in one. That answer comes out of plan review for the address. Buying a building with this plan in mind? Call or text (240) 222-5257 with the address and a photo of the upstairs before you close, and we will tell you what the conversion is likely to bring with it.

Which standard the building gets

Two standards cover almost every job like this. NFPA 13 is the full commercial standard, and mixed use buildings are built to it. NFPA 13R is the standard for residential buildings up to four stories. It is designed around getting people out of the living spaces, so it leaves heads out of some spaces that a full NFPA 13 system covers. That makes the two different amounts of pipe in the same footprint.

What the building ends up asHow the code sees itStandard to plan on
Shop, office or restaurant stays on the street floor, apartments go in aboveMixed useNFPA 13, the full commercial standard, in the shop and the apartments
The whole building becomes apartments, four stories or fewerResidential onlyNFPA 13R is allowed, inside the building code’s own height limits
The whole building becomes apartments, more than four storiesResidential onlyNFPA 13
The building is rebuilt as a one or two family houseA houseNFPA 13D, the home standard

The plan reviewer confirms the standard, and it has to be settled before anyone prices the job. Our commercial installation guide walks through how the counties handle the two as separate submittals. Text the code summary sheet from the architect’s set, or a phone photo of it, to (240) 222-5257 and we will tell you which row the building lands in.

What the unit count does

The unit count moves the building between system classes. A rowhouse rebuilt as a one or two family house stays in the home standard, NFPA 13D, which our Baltimore rowhouse guide covers. Put three or more dwelling units under one roof and the building leaves that class. Add a shop below those units and it is mixed use.

So two apartments over a shop and six apartments over a shop are the same kind of problem, and the count changes the size of it. More units means more rooms, more heads, more water and a bigger alarm. Count the units on the plans, including the one somebody wants to add in the back later.

The water service on an old main street building

Water is where these jobs get decided. A building that has only ever fed a shop sink and a bathroom has a small service, and a city rowhouse is often on a three quarter inch line under the street. A sprinkler system for a shop and apartments asks a lot more of the service than the fixtures ever did, so the size of that line and the strength of the main are the first things we check.

The counties want the water proven on paper. Montgomery County asks for a flow test taken inside the building, no more than a year old, on an existing service, because nobody knows the condition of the old underground pipe. Anne Arundel County wants a fire flow test by its Department of Public Works within 12 months of the application. A fire pump is the answer only when the public supply is shown to fall short, and it is the largest add on any job. Have a water bill, a meter photo or just the address? Text it to (240) 222-5257 and we will tell you what the service has to carry before anyone draws a line.

The alarm tie in

A sprinkler system in a building like this reports to a fire alarm panel. The flow switch and the valve supervision are wired to it, the alarm is a separate permit and a separate trade, and both have to be ready for the same final. Anne Arundel County expects the sprinkler system tied into the fire alarm at the final inspection. Baltimore County goes further and will only take a commercial alarm from a listed installer, which our guide to the UL certificate rule explains. Put the alarm in the budget on day one. Not sure who carries it on your job? Call or text (240) 222-5257 with the plans and we will lay out which trade owns which piece.

The permit order, county by county

The sprinkler permit is its own application with its own review, and the order matters to the schedule.

On every one of these the licensed sprinkler contractor on the job designs the system, installs it and pulls the permit. The pipe goes in while the walls and ceilings are open, so the sprinkler drawings need to be moving before the framing crew starts upstairs.

What to send for a number

The standard, the water service and the ceilings move the price more than the square footage does, and the ranges we publish are on the cost page. Call or text (240) 222-5257 with the address and those photos and we will send a written quote that says what is included. For the years after the building opens, our page on commercial fire sprinkler systems in Maryland covers the yearly inspection and the backflow test.